stat

Top  Previous  Next
Got to CoolMaster 1000D page

SYNOPSIS

       stat [UID]

 

DESCRIPTION

Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request, response will contain information about all units

 

EXAMPLE

>stat                          

100 ON  12C 12,41C High Cool OK

101 OFF 32C 04,93C Low  Dry  OK

102 ON  07C 08,27C High Dry  OK

103 OFF 01C 26,84C Med  Dry  OK

104 ON  04C 24,08C High Dry  OK

105 OFF 11C 07,23C Low  Dry  OK

106 ON  11C 14,91C Auto Dry  OK

107 ON  27C 12,94C Med  Cool OK

OK                             

>stat 101                      

101 OFF 32C 04,93C Low  Dry  OK

OK                             

 

RESPONSE

Position in String

Example

Format

Description

0-2

109

NNN

Indoor unit Centralized Address

4-6

ON

ON or OFF

On/Off Status

8-10

23C

NNC

Set Temperature ºC

12-17

24,08C

NN,NNC

Room Temperature ºC

20-23

Auto

Low or Med or High or Auto

Fan Speed

25-28

Cool

Cool or Heat or Fan or Dry

Operation Mode

30-32

OK

OK or XN

OK or Failure code

 

EXIT CODE

OK

Request Successfully Executed

ERROR:1

Unit with specified UID not found

 

COMPATIBILITY

CoolMaster 1000D

v 0.0.1

CoolMaster 2000S

v 2.0.9

This command is obsolete and is supported only for backward compatibility.