stat3

Top  Previous  Next
Got to CoolMaster 1000D page

SYNOPSIS

       stat3 [UID]

 

DESCRIPTION

Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request, response will contain information about all units. stat3 compared to stat2 has no fractional part in the room temperature presentation.

 

EXAMPLE

>stat3                        

100 ON  12C 12C High Cool OK 0

101 OFF 32C 04C Low  Dry  OK 1

102 ON  07C 08C High Dry  OK 0

103 OFF 01C 26C Med  Dry  OK 0

104 ON  04C 24C High Dry  OK 0

105 OFF 11C 07C Low  Dry  OK 0

106 ON  11C 14C Auto Dry  OK 0

107 ON  27C 12C Med  Cool OK 1

OK                            

>stat3 101                    

101 OFF 32C 04C Low  Dry  OK 0

OK                            

 

RESPONSE

Position in String

Example

Format

Description

0-2

109

NNN

Indoor unit Centralized Address

4-6

ON

ON or OFF

On/Off Status

8-10

23C

NNC

Set Temperature ºC

12-14

24C

NNC

Room Temperature ºC

16-19

Auto

Low or Med or High or Auto

Fan Speed

21-24

Cool

Cool or Heat or Fan or Dry

Operation Mode

26-27

OK

OK or XN

OK or Failure code

29

0

0 or 1

Filter Reset Sign present

 

EXIT CODE

OK

Request Successfully Executed

ERROR:1

Unit with specified UID not found

 

COMPATIBILITY

CoolMaster 1000D

v 2.0.9

CoolMaster 2000S

v 2.0.9